Special Control SiUS28-902_a
21 Function
3. Special Control
3.1 Startup Control
On activation, the following control is performed to lighten the load of the compressor with liquid
refrigerant located at the compressor at startup. Also, the position of the four-way valve is
defined.
3.1.1 Startup Control in Cooling Operation
3.1.2 Startup Control in Heating Operation
Actuator Operation Remarks
Compressor Differential pressure control
Compressor operating frequency
increases by 2 step / 20 sec. until
Pc - Pe>58 psi.
Outdoor unit fan High pressure control
Initial fan speed is set to STEP 0.
1-step increase with Pc>305 psi
1-step decrease with Pc<261 psi
Four-way valve OFF
Main electronic expansion valve (EV1) 1400 pls
Subcooling electronic expansion valve
(EV2)
0 pls
Hot gas bypass valve (SVP) ON
Receiver gas discharging valve (SVG) OFF
Ending conditions
230 sec.
Pc - Pe>58 psi
45 sec.
Actuator Operation Remarks
Compressor Differential pressure control
Compressor operating frequency
increases by 2 step / 20 sec. until
Pc - Pe>58 psi
Outdoor unit fan STEP 8
Four-way valve ON
Main electronic expansion valve (EV1) 180 pls
Subcooling electronic expansion valve
(EV2)
0 pls
Hot gas bypass valve (SVP) ON
Receiver gas discharging valve (SVG) OFF
Ending conditions
145 sec.
Pc - Pe>58 psi
15 sec.
or
&
(
or
&
(