SiUS28-902_a Operation Mode
Function 16
1. Operation Mode
Operation in
stop mode
Pressure
equalization
prior to startup
Startup control
• Cooling startup
control
• Heating startup
control
Oil return IN
conditions are met.
Operation
mode c
hange
Oil return operation
Pump-down
residual
operation
Restart standby
(Compressor stop)
Yes
Yes
No
No
Malfunction/Standby
Indoor unit stop or
thermostat OFF
Normal operation
• Compressor PI control
• Electronic expansion
valve PI control
• Protection control
Indoor unit thermostat ON
Defrost IN
conditions are met.
No
Yes
Defrosting operation
Cooling or heating
operation
Indoor unit thermostat ON
Indoor unit stop or
thermostat OFF
Indoor unit stop or
thermostat OFF
Malfunction/
Standby
Malfunction/
Standby
Note:
In the event indoor unit stops or the thermostat
turns OFF while in oil return operation or
defrosting operation, pump-down residual
operation is performed on completion of the oil
return operation or defrosting operation.