EasyManua.ls Logo

Daikin FCQ18PVJU - UE Malfunction of Transmission between Centralized Remote Controller and Indoor Unit

Daikin FCQ18PVJU
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiUS28-902_a Troubleshooting by Indication on the Remote Controller
Troubleshooting 138
3.41 UE” Malfunction of Transmission between Centralized
Remote Controller and Indoor Unit
Remote
Controller
Display
UE
Applicable
Models
AII indoor unit models
Centralized controller
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized remote controller is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control and indoor
unit
Connector for setting master controller is disconnected.
Failure of P.C.B. for centralized remote controller