EasyManua.ls Logo

Daikin FDEQ100B7V3B - Overview of the Indoor Safety Devices

Daikin FDEQ100B7V3B
390 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting ESIE05-04
3–30 Part 3 Troubleshooting
3
1
3
4
5
1.10 Overview of the Indoor Safety Devices
Thermal protector Thermal fuse fan motor
Abnormal Reset (automatic)
FCQ35, 50, 60, 71B >130°C +/-5°C <83°C +/-20°C N.A.
FCQ100, 125B >140°C +/-5°C <45°C +/-15°C N.A.
FCQ71, 100, 125, 140D N.A. N.A. N.A.
FFQ25, 35, 50, 60B >130°C +/-5°C <83°C +/-20°C N.A.
FBQ35, 50, 60, 71,100, 125B N.A. N.A. >152 +/-2°C
FDQ125, 200, 250B N.A. N.A. >160 °C
FHQ35, 50, 60, 71, 100, 125B >130°C +/-5°C <83°C +/-20°C N.A.
FUQ71, 100, 125B >130°C +/-5°C <83°C +/-20°C N.A.
FAQ71, 100B >130°C +/-5°C <83°C +/-20°C N.A.
FDEQ71, 100, 125B N.A. N.A. >152 +/-2°C

Table of Contents