SiUS122226E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 191
Note
7.4 Unspecified Voltage (Between Indoor Unit and Outdoor
Unit), Anti-icing Control in Other Rooms
Error Code UA, UH
Outdoor Unit LED
Display
A j 1 h 2 h 3 h 4 h 5 h
Method of Error
Detection
A wrong connection is detected by checking the combination of indoor and outdoor units on the
microcomputer.
Error Decision
Conditions
Anti-icing control in other rooms
Unspecified internal and/or external voltages
Mismatching of indoor and outdoor units
Supposed
Causes
Anti-icing function in other rooms
Power supply voltage out of specification
Wrong models interconnected
Wrong indoor unit PCB or outdoor unit PCB mounted
Troubleshooting
Refer to Anti-icing control for indoor unit on page 192 for details.
(R21922)
Caution
NO
YES
NO
YES
NO
YES
Check the model combination.
Error displayed
while operating?
Power supply
voltage as specified?
Matched
compatibly?
The anti-icing function is
activated in other rooms.
Refer to A5.
Correct the power supply
voltage.
Match the compatible models.
Check the combination of all
connected models.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Table of Contents

Other manuals for Daikin FDMQ15WVJU9

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FDMQ15WVJU9 and is the answer not in the manual?

Daikin FDMQ15WVJU9 Specifications

General IconGeneral
ModelFDMQ15WVJU9
CategoryAir Conditioner
Coefficient of Performance (Heating)3.5
RefrigerantR410A
Weight9 kg
Power SourceElectric
Indoor Unit Weight9 kg
Operating Temperature (Heating)-15°C to 24°C

Related product manuals