25
Engineering & Physical Data
MODEL
INDOOR FHYC40EXV1
OUTDOOR RY35DXV1 RY40DXV1 RY40DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 2937 / 426
CLOSE kPa / psi 2413 / 350
LOW PRESSURE
SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
PHASE SEQUENCER N/A YES
DISC. THERMOSTAT SETTING °C / F N/A N/A 130 / 266
MODEL
INDOOR FHYC50EXV1
OUTDOOR R50DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 2937 / 426
CLOSE kPa / psi 2413 / 350
LOW PRESSURE
SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
PHASE SEQUENCER YES
DISC. THERMOSTAT SETTING °C / F 130 / 266
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
DAIKIN_FF_FHC.indb 25DAIKIN_FF_FHC.indb 25 9/27/2012 2:04:54 PM9/27/2012 2:04:54 PM