EDUS091617 Electric Characteristics
Split Type Air Conditioners FFQ-Q Series 29
10.Electric Characteristics
3D106058
Unit Combination Power Supply Compressor OFM IFM
Indoor Unit Outdoor Unit Hz - Volts Voltage Range MCA MFA RLA W FLA W FLA
FFQ09Q2VJU RX09QMVJU
60 - 208
Max. 253 V
Min. 187 V
8.6 15 7.5 18 0.15 50 0.28
60 - 230
FFQ12Q2VJU RX12QMVJU
60 - 208
Max. 253 V
Min. 187 V
8.6 15 7.5 18 0.15 50 0.28
60 - 230
FFQ15Q2VJU RX15QMVJU
60 - 208
Max. 253 V
Min. 187 V
9.1 15 8.0 59 0.39 50 0.28
60 - 230
Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is the max current that comes in cooling operation and heating
operation.
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Be sure to install a ground leak detector.
(This unit uses an inverter, which means that a ground leak detector
capable of handling high harmonics must be used in order to prevent
malfunctioning of the ground leak detector.)
MFA : Max. fuse amps (A)
RLA : Rated load amps (A)
OFM : Outdoor fan motor
IFM : Indoor fan motor
W : Fan motor rated output (W)
FLA : Full load amps (A)