Error Codes: System Malfunctions ESIE05-04
3ā50 Part 3 ā Troubleshooting
3.5 Malfunctioning Field Setting Switch (
)
Error code UA
Error generation The error is generated when incorrect field settings have been set for pair/twin/triple/double twin.
Causes The possible causes are:
Q Malfunctioning indoor or outdoor unit PCB
Q Malfunctioning power supply PCB
Q Indoor-outdoor, indoor-indoor unit transmission wiring
Q Malfunctioning remote controller wiring.