Loading...
Disassembly and Maintenance ESIE05-04
5–66 Part 5 – Disassembly and Maintenance
3
1
5
5
1.12.12 Replacement of Heat Exchanger
Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step Procedure Points
1 Removing the heat
exchanger
1 Remove the refrigerant
pipe after completion of
refrigerant collection and
pump down operation.
Q This work should be performed
with two personnel including
one person for supporting the
heat exchanger to avoid falling
down during the work.
2 Remove the fixing plate
of heat exchanger.
3 Remove the pipe fixing
plate mounted with two
screws.
(S2675)
Heat exchanger
fixing plate
Pipe fixing
plate
(S2676)