EasyManuals Logo

Daikin FHC30NUV2S User Manual

Daikin FHC30NUV2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #105 background imageLoading...
Page #105 background image
Si20-701_B Troubleshooting by Remote Controller
98
3.9
A7
Swing Flap Motor
Abnormality / Lock
Remote Controller Display
A7
Applicable Models
FH(Y)C, FH(Y)K, FH(Y), FA(Y), FV(Y), FUY, FHC, FH,
FDBG, FDBT, FDMG, FCQ(H), FMCQ, FFQ, FHQ,
FAQ(except FAQ71BU), FBQ, FUQ, FVQ
Method of Error Detection
The error is detected by the limit switch when the motor
turns.
Error Decision Conditions
When ON/OFF of the micro-switch for position detection
cannot be reversed even though the swing flap motor is
energized for a specified amount of time (about 30
seconds).
Supposed Causes
îš„ Defective swing flap motor
îš„ Defective micro-switch
îš„ Defective connector connection
îš„ Defective indoor unit PCB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FHC30NUV2S and is the answer not in the manual?

Daikin FHC30NUV2S Specifications

General IconGeneral
BrandDaikin
ModelFHC30NUV2S
CategoryAir Conditioner
LanguageEnglish

Related product manuals