Si20-701_B Troubleshooting by Remote Controller
472
Pressure Sensor for RZQ(S)-B, RZQ-C7 and CMSQ
High Pressure (PH)
Low Pressure (P
L)
PH = 1.38VH-0.69
P
L = 0.57VL-0.28
P
H: High pressure (MPa)
P
L: Low pressure (MPa)
V
H: Output Voltage [High Side] VDC
VL: Output Voltage [Low Side] VDC
Output Voltage (VH, VL)
Detected Pressure