EasyManuals Logo

Daikin FHC30NUV2S User Manual

Daikin FHC30NUV2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #263 background imageLoading...
Page #263 background image
Si20-701_B Troubleshooting by Remote Controller
256
3.54
JA
High Pressure Sensor
Abnormality
Remote Controller Display
JA
Applicable Models
RZQ, CMSQ
Method of Error Detection
The error is detected from the pressure detected by the
high pressure sensor.
Error Decision Conditions
When the high pressure sensor is short circuit or open
circuit
Supposed Causes
îš„ Defective high pressure sensor
îš„ Connection of low pressure sensor with wrong
connection
îš„ Defective outdoor unit PCB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FHC30NUV2S and is the answer not in the manual?

Daikin FHC30NUV2S Specifications

General IconGeneral
BrandDaikin
ModelFHC30NUV2S
CategoryAir Conditioner
LanguageEnglish

Related product manuals