EasyManuals Logo

Daikin FHC30NUV2S User Manual

Daikin FHC30NUV2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #497 background imageLoading...
Page #497 background image
Si20-701_B Troubleshooting by Remote Controller
490
1. Power module checking
When using the analog type of multiple tester, make
measurement in resistance measurement mode in
the x1k
Ω
range.
No.
Measuring point
Criterion Remark
+-
1P3 U
2 to 15kΩ2P3 V
3P3 W
4U P3
Not less
than
15kΩ
(including)
It may take
time to
determine the
resistance due
to capacitor
charge or else.
5V P3
6W P3
7N3 U
8N3 V
9N3 W
10 U N3
2 to 15kΩ11 V N3
12 W N3
When using the digital type of multiple tester, make
measurement in diode check mode ( ).
No.
Measuring point
Criterion Remark
+-
1P3 UNot less
than
1.2V
(including)
It may take time to
determine the voltage
due to capacitor
charge or else.
2P3 V
3P3 W
4U P3
0.3 to 0.7V
5V P3
6W P3
7N3 U
8N3 V
9N3 W
10 U N3 Not less
than
1.2V
(including)
It may take time to
determine the voltage
due to capacitor
charge or else.
11 V N3
12 W N3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FHC30NUV2S and is the answer not in the manual?

Daikin FHC30NUV2S Specifications

General IconGeneral
BrandDaikin
ModelFHC30NUV2S
CategoryAir Conditioner
LanguageEnglish

Related product manuals