Troubleshooting by Remote Controller Si20-701_B
297
3.67
L8
Inverter Current
Abnormality
Remote Controller Display
L8
Applicable Models
CMSQ
Method of Error Detection
The error is detected by current flowing in the power
transistor.
Error Decision Conditions
When overload in the compressor is detected. (Inverter
secondary current 16.1A)
Supposed Causes
îš„ Compressor overload
îš„ Compressor coil disconnected
îš„ Defective inverter PCB
îš„ Defective compressor