EasyManuals Logo

Daikin FHC30NUV2S User Manual

Daikin FHC30NUV2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
Troubleshooting by Remote Controller Si20-701_B
117
∗2. Method to check transmission part of indoor unit
PCB.
1 Turn OFF the power and remove the connecter
X70A of indoor unit PCB.
2 Short circuit X70A.
3 After turning ON the power, check below numbers
under local setting remote control. (Confirmation:
Second code No. at the condition of first code No.
21 on mode No. 41)
↓
∗ After confirmation, turn OFF the power, take off the
short circuit and connect X70A back to original
condition.
Determination 01: Normal
Other than 01: Transmission defect
on indoor unit PCB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FHC30NUV2S and is the answer not in the manual?

Daikin FHC30NUV2S Specifications

General IconGeneral
BrandDaikin
ModelFHC30NUV2S
CategoryAir Conditioner
LanguageEnglish

Related product manuals