EasyManuals Logo

Daikin FHC30NUV2S User Manual

Daikin FHC30NUV2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #247 background imageLoading...
Page #247 background image
Si20-701_B Troubleshooting by Remote Controller
240
Remote Controller Display
H9
Applicable Models
RZ(Y), CMSQ
Method of Error Detection
The detection is based on abnormal resistance value of
the thermistor.
Error Decision Conditions
When the outdoor air thermistor has short circuit or open
circuit.
Supposed Causes
îš„ Defective outdoor air thermistor
îš„ Defective connection of outdoor air thermistor
connector
îš„ Defective outdoor unit PCB
Troubleshooting
YES
Is
connector
connected to the
outdoor unit
PCB?
NO
YES
Connect the
thermistor, and
operate the unit.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
NO
Disconnect
thermistor from
outdoor unit PCB, and
measure resistance.
Is resistance
normal?
Replace the
thermistor.
Replace the
outdoor unit
PCB.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FHC30NUV2S and is the answer not in the manual?

Daikin FHC30NUV2S Specifications

General IconGeneral
BrandDaikin
ModelFHC30NUV2S
CategoryAir Conditioner
LanguageEnglish

Related product manuals