EasyManuals Logo

Daikin FHC30NUV2S User Manual

Daikin FHC30NUV2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #413 background imageLoading...
Page #413 background image
Si20-701_B Troubleshooting by Remote Controller
406
Remote Controller Display
U5
Applicable Models
RZ(Y)
Method of Error Detection
Micro-computer checks if transmission between indoor
unit and remote controller is normal.
Error Decision Conditions
When transmission is not carried out normally for a
certain amount of time
Supposed Causes
îš„ Defective remote controller
îš„ Defective indoor unit PCB
îš„ External factor (Noise, etc.)
îš„ Connection of 2 main remote controllers (When using
2 remote controllers)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FHC30NUV2S and is the answer not in the manual?

Daikin FHC30NUV2S Specifications

General IconGeneral
BrandDaikin
ModelFHC30NUV2S
CategoryAir Conditioner
LanguageEnglish

Related product manuals