EasyManua.ls Logo

Daikin FTK24AXVJU - Standby Electricity Saving (Suspend Function); Controls at Mode Changing;Start-Up

Daikin FTK24AXVJU
119 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DAMA-SM-21-001 Control Specification
Functions and Control 37
3.3 Standby Electricity Saving (Suspend Function)
Outline
This function is to save standby electricity consumption while the air conditioner is not in operation
by partially separating the electrical circuit of indoor and outdoor units from the power source.
Details Standby electricity saving function can be activated/deactivated from the service mode of
the remote controller.
When standby electricity saving is ON, the system enters suspend state if both indoor and
outdoor units are not in operation.
The system will not go into suspend state when some voltage is applied to the outdoor unit
for protection purpose even if the indoor unit is not in operation.
In suspend state, power supply to the outdoor unit is halted and there is no communication
between the indoor unit and the outdoor unit.
Also the service monitor LED (LED A) lights off.
To return from the suspend state, start fan or other operation to turn on the indoor unit.
3.4 Controls at Mode Changing/Start-up
3.4.1 3-Minute Standby
Turning on the compressor is prohibited for 3 minutes after turning off.
3.4.2 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(sec.)
Time
(Hz)
Frequency
72Hz
90Hz
112Hz
FTK(X)09/12
54Hz
180 420 180 120 1
40Hz
(sec.)
Time
(Hz)
Frequency
FTK(X)18/24
120 200 470 0
85Hz
70Hz
55Hz

Table of Contents

Other manuals for Daikin FTK24AXVJU

Related product manuals