DAMA-SM-21-001 Actuator Check
Service Diagnosis 90
5.5 Inverter Unit Refrigerant System Check
Check No.14
5.6 Rotation Pulse Check on the Outdoor Unit PCB
Check No.16 Make sure that the voltage of 320 + 100 V ~ 320 - 50 V is applied.
1. Set operation off and power off. Disconnect the connector S70 or S71.
2. Check that the voltage between the pins 4 - 7 is 320 VDC.
3. Check that the control voltage between the pins 3 - 4 is 15 VDC.
4. Check that the rotation command voltage between the pins 2 - 4 is 0 ~ 6.5 VDC.
5. Keep operation off and power off. Connect the connector S70 or S71.
6. Check whether 4 rotation pulses (0 ~ 15 VDC) are input at the pins 1 - 4 when the fan motor
is rotated 1 turn by hand.
When the fuse is melted, check the outdoor fan motor for proper function.
If NG in step 2 Defective PCB Replace the outdoor unit PCB (main PCB).
If NG in step 4 Defective Hall IC Replace the outdoor fan motor.
If OK in both steps 2 and 4 Replace the outdoor unit PCB (main PCB).
Applicable for FTK(X)09/12/18/24
Refrigerant system check
Is the discharge pipe
thermistor disconnected from
the holder?
Check for refrigerant leakage.
See the section on refrigerant
shortage detection.
YES
NO
Reconnect the thermistor.
Replace the refrigerant.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
PCB
Actual rotation pulse input (0 ~ 15 VDC)
Rotation command voltage (0 ~ 6.5 VDC)
Control voltage 15 VDC
S71 or S71
320 VDC
(R20507)
1
2
3
4
5
6
7