System control Si18-201
156 Main Functions
The motorized valve operating amount is determined based on deviation EGA between each
room unit's gas pipe temperature and of DGAV after GFTUYU correction and previous deviation
EGAZ.
(Example) The following example is based on room A.
EGA = DGA - DGAV
When the operating flow rate of EVA is QRGA
QRGA = KPCB (0.05) × ((EGA-EGAZ) + KIB (0.32) × (EGA + EGAZ))
= 0.05 × (EGA - EGAZ) + 0.016 × (EGA + EGAZ)
When QRGA
QHENC(-0.12), the following condition is set: QRGA
QHENC (-0.12 Nm³/
hr).
Outside Air Temperature Gas Pipe Lower-Limit Temperature
-5 0
01
52
10 3
15 4
20 5
25 6
30 7
35 8
40 9
45 10