3.3.4 3-minutes Standby
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(except when defrosting)
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as follows.
(The function must not be used when defrosting.)
3.4 Discharge Pipe Temperature Control
Outline The discharge pipe temperature is used as the compressor's internal temperature. If the discharge
pipe temperature rises above a certain level, the operating frequency upper limit is set to keep this
temperature from going up further.
Detail Divide the Zone
Management within the Zones
FCG 3
FCG 2
FCG 1
TCG1
TCG2
TCG3
88
64
48
240
360
180
Zone Control contents
Stop zone When the temperature reaches the stop zone, stop the compressor and
correct abnormality.
Drooping zone Start the timer, and the frequency will be drooping.
Keep zone Keep the upper limit of frequency.
Return / Reset zone Cancel the upper limit of frequency.