Sound Data
Model
(MSP)
Speed
1/1 Octave Sound Pressure Level (dBA, reference 20mPa) Overall
Noise
Criteria
125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA)
FWC03G
High 46 36 33 31 24 16 10 36 30
Med 42 30 27 24 15 9 9 30 23
Low 35 21 16 13 8 8 7 22 0
FWC04G
High 40 38 37 32 28 20 15 38 32
Med 37 34 31 26 20 13 10 32 25
Low 27 25 22 16 9 9 9 23 0
FWC06G
High 47 44 40 36 31 22 13 42 35
Med 44 40 37 32 26 16 10 38 32
Low 38 34 31 26 18 10 10 32 25
FWC08G
High 49 45 42 37 33 27 18 44 37
Med 45 41 36 31 26 19 11 38 31
Low 39 33 30 23 16 12 9 31 24
FWC10G
High 52 47 42 38 33 26 19 45 37
Med 49 43 39 34 29 22 13 41 34
Low 42 37 32 27 21 12 9 34 26
FWC12G
High 49 46 43 40 34 26 18 45 39
Med 45 42 41 35 29 19 11 41 36
Low 43 40 36 33 25 14 10 38 32
FWC14G
High 54 49 46 41 38 32 26 48 41
Med 51 45 42 38 34 27 20 44 37
Low 43 36 36 29 23 15 8 36 31
FWC16G
High 57 51 46 42 37 32 29 49 41
Med 54 48 43 38 33 27 22 45 38
Low 48 40 37 30 25 16 10 38 32
FWC18G
High 58 52 46 43 42 36 33 50 43
Med 55 48 43 38 36 32 28 46 39
Low 52 41 36 32 30 24 18 40 35
FWC20G
High 58 53 47 45 40 35 32 51 44
Med 56 50 44 40 35 30 27 47 40
Low 50 41 36 32 27 19 14 39 33
Microphone position: 1.5m below the centre of the unit.
(Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).