Forced Operation Mode SiBE611027_A
75 Trial Operation and Field Settings
1. Forced Operation Mode
Outline After installation, carry out the forced operation and make the water valve open to purge air.
Detail
Start Press the forced operation ON/OFF button (SW1) on the indoor unit for
5 seconds.
Operation Operation mode: FAN
Airflow rate: H tap
Water valve: full open
End The forced operation ends when any of the following conditions is fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced operation ON/OFF button (SW1) on the indoor unit again.
3) Press the ON/OFF button on the remote controller.
ON / OFF button (SW1)
(R12775)