EasyManuals Logo

Daikin MicroTech III Sales And Engineering Data Sheet

Daikin MicroTech III
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER 20 www.DaikinApplied.com
ComprehensIve daTa Tables
Table 13: Multi-State Values - SmartSource Single and Two Stage, Ennity Large Two Compressor
Point Name
Object
Type/
Instance
Read/
Write
Access
2
BACnet Object
Name
Range/Default
(in Units)
Non-
volatile
Memory
1
Description
MULTI-STATE VALUES
Compressor Enable
Input
MSV:1 C ComprEnable
1 to 3
Default: 3
N
Species if the compressor(s) are allowed to operate, which
can be based on proof of loop uid ow. The loop pump
must be running to provide adequate ow through the unit
so the compressor(s) can operate safely. The network
override will revert back to its default value upon unit
controller reboot.
1 = Disabled
2 = Enabled
3 = Null (compressors are enabled)
Current Alarm MSV:2 R CurrentAlarm
SmartSource
(Series2)
1 to 16
Ennity Large
Two Compressor
(SS2C)
1 to 20
N
Displays the current highest priority active alarm
SmartSource (Series2) Alarms
1 = No Alarms
2 = IO Exp Communication Fail
3 = Invalid Conguration
4 = Low Voltage Brownout
5 = Comp High Pressure
6 = Comp Low Pressure
7 = Comp Suction Temp Snsr Fail
8 = Comp Low Suction Temp
9 = Freeze Fault Detect
10 = Room Temp Sensor Fail
11 = Enter Water Temp Snsr Fail
12 = Leaving Water Temp Snsr Fail
13 = Condensate Overow
14 = Low Entering Water Temp
15 = Serial EEPROM Corrupted
16 = Wtrside Econ Low Temp Cutout
Ennity Large Two Compressor (SS2C) Alarms
1 = No Alarms
2 = IO Exp Communication Fail
3 = Invalid Conguration
4 = Low Voltage Brownout
5 = Comp#1 High Pressure
6 = Comp#2 High Pressure
7 = Comp#1 Low Pressure
8 = Comp#2 Low Pressure
9 = Comp#1 Suctn Temp Snsr Fail
10 = Comp#2 Suctn Temp Snsr Fail
11 = Comp#1 Low Suction Temp
12 = Comp#2 Low Suction Temp
13 = Freeze Fault Detect
14 = Room Temp Sensor Fail
15 = Entering Water Temp Sensor Fail
16 = Leaving Water Temp Snsr Fail
17 = Condensate Overow
18 = Low Entering Water Temp
19 = Serial EEPROM Corrupted
20 = Wtrside Econ Low Temp Cutout
Fan ON/Auto Remote
Input
MSV:3 C RemoteFanOnAuto
1 to 3
Default: 3
N
Overrides the local fan ON/Auto room sensor and
thermostat switch inputs. The local Fan ON/Auto Switch
is only used when MSV:3 is set to 3 (Null). The network
override will revert back to its default value upon unit
controller reboot.
1 = Fan Auto (forces cycling fan)
2 = Fan On (forces fan on)
3 = Null (no override)
McQuay WSHP Status MSV:4 R McQWSHPStatus 1 to 10 N
Indicates the unit’s operating state.
1 = Off Alarm
2 = Off
3 = Start
4 = Fan Only (fan is allowed to operate)
5 = Prepare to Heat
6 = Heating
7 = Prepare to Cool
8 = Cooling
9 = Prepare to Dehumidify
10 = Dehumidication

Table of Contents

Other manuals for Daikin MicroTech III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech III and is the answer not in the manual?

Daikin MicroTech III Specifications

General IconGeneral
BrandDaikin
ModelMicroTech III
CategoryController
LanguageEnglish

Related product manuals