OM 1280-2 • MICROTECH UNIT CONTROLLER 64 www.DaikinApplied.com
Table 29: Local User Interface (LUI) Parameters
Menu Name
(Menu Index)
Minimum Password to Read
(None, User, Manager, Technician)
Minimum Password to Write
(None, User, Manager, Technician)
“RO” if Read Only
Help Text
Live
MSM: T RO Main State Machine (MSM) state.
CntrlTmp: N RO Selected temp, either space or RAT.
N RO
N RO Actual occupancy mode of unit.
PWLevel: N RO Current password level.
EnterPW: N N Enter a new password.
ClearPW: N U Clear the password level to NONE.
UnitStatus
MSM: T RO Main State Machine (MSM) state.
MSM: N RO
Main State Machine (MSM) state. Duplicate of MSM parameter. Displayed as
enumerated text.
Prev1MSM: T RO Previous 1 Main State Machine state.
Prev2MSM: T RO Previous 2 Main State Machine state.
Prev3MSM: T RO Previous 3 Main State Machine state.
Prev4MSM: T RO Previous 4 Main State Machine state.
AppModeCmd: N RO System status command.
KeyAppMode: N U Keypad heat/cool command.
N RO Actual heat/cool mode of unit.
EnergHold: N U
NetEnrgHld: N RO
KeyEnrgHld: N U
NetEmergOv: N RO Network emergency override.
KeyEmergOv: N M Keypad emergency override.
AllowHeat: T RO Heating allowed status.
AllowCool: T RO Cooling allowed status
AllowDehum: T RO
RONgtPrgTmr: N RO Night purge count down timer.
N RO Mode is: Heat, Cool or None.
AuxHt: N RO
EmergOvRes: N RO Emergency override result.
OnStop: N RO Keypad On/Stop status.
LowOAFrzStat: T RO
ValveFrzProt: T RO Actv if LowOAFrzStat Actv and F&B clsd.
T RO
Occupancy
N RO Actual occupancy mode of unit.
KeyOccManCmd: N U Keypad occupancy override command.
NetOccManCmd: N RO Network occupancy override command.
NetOccSensor: N RO Network occupancy sensor.
NtOccSched: N RO Network occupancy schedule command.
TenantOver: N RO Tenant Override start trigger.
Temperatures
SpaceTemp: N RO Current space temperature.
RAT: T RO Analog input return/room air temp.
CntrlTmp: N RO Selected temp, either space or RAT.
OAT: N RO Outside air temperature.
DAT: N RO Discharge air temperature.
N RO Entering Water Temperature.
LW T: N RO Leaving Water Temperature.
InAirCoilDx: N RO Indoor air/DX coil temperature.
OutArCoilDx: N RO Outdoor air/DX coil temperature.
CntrlTmpSt: N RO Cool, heat, between or invalid.
NetSpcTemp: N RO Network space temperature.
NetOAT: N RO Network outside air temperature.
NetEWT: N RO Network Entering Water Temperature.
Setpoints
N RO
NetSetpt: N RO Network setpoint.
Setpoint: N RO Current setpoint.
ClgSpt: N RO Current cooling setpoint
HtgSpt: N RO Current heating setpoint
N RO
LocSptShft: N RO Local hardwired setpt shift.
N RO
N RO
N RO
NtOccClSptSh: N RO Net Occupied cooling setpoint shift.
NtStdClSptSh: N RO Net Standby cooling setpoint shift.