www.DaikinApplied.com 65 OM 1280-2 • MICROTECH UNIT CONTROLLER
Menu Name
(Menu Index)
Minimum Password to Read
(None, User, Manager, Technician)
Minimum Password to Write
(None, User, Manager, Technician)
“RO” if Read Only
Help Text
NtOccHtSptSh: N RO Net Occupied heating setpoint shift.
NtStdHtSptSh: N RO Net Standby heating setpoint shift.
IndoorFan
CurFanSpd: N RO Current indoor fan speed.
FanState: N RO Indoor fan running state.
KeyInFan: N U Keypad manual indoor fan override.
NetFanSpdCmd: N RO Network Fan spd cmd. Not 0 to 100 for Auto.
CalcFanSpd: T RO Calculated indoor fan speed.
SZnVAVFanPI: T RO Single zone VAV fan speed PI out.
Compressor
NetCmpEn: N RO Network compressor enable.
ClOATLckStat: N RO ASHP: Status of OAT Comp clg lock-out.
CmpHtOATLckSt: N RO ASHP: Status of OAT comp htg lock-out.
CmpHtEWTLckSt: N RO WSHP: Status of EWT comp htg lock-out.
CompOnTmr: N RO Seconds since compressor was turned on.
N RO
PumpCmd: N RO Pump command.
CmpClAvl: N RO
CmpHtAvl: N RO
CmpStgCmd: T RO Commanded comp cool stages.
RevVlvCmd: T RO Commanded reversing valve.
RevVlvStat: N RO Reversing valve status.
CmpStartDly: M T Timer after powerup before comp turn on.
CondEcmFanOut: N RO Condenser fan output.
DfrstSt: N RO Current defrost state.
LLCmpStgCmd: T RO LowLimit/Reheat commanded comp stgs.
MSMRevVlvCmd: T RO MSM commanded reversing valve.
MSMCmpStgCmd: T RO MSM commanded comp stages.
MSMPumpCmd: T RO MSM Pump command.
EmHtCmpStgCmd: T RO Emergency heat commanded comp stages.
RandomStrtTm: T T Dly after powerup before comp turn on.
HydroHeating
HotWtr: N RO Hot water valve position.
HydroHtAvl: N RO
EwtHtState: M RO EWT hydronic heating state.
EwtFlwHtTmr: T RO
DATLLHWPI: T RO DAT hot water lower limit PI.
HWVlvMxTout: T RO Hot water valve maxed for 3 minutes.
HydroCooling
ColdWtr: N RO Cold water valve position.
HydroClAvl: N RO
EwtClState: M RO EWT hydronic cooling state.
EwtFlwClTmr: T RO
OADamper
OADPos: N RO Outside air damper position.
OADMinPos: N RO Current OAD minimum position calc.
SpcCO2: N RO CO2 level in the space
EconMode: N RO Economizer mode.
OADLowTmpStat: M RO OA damper low temperature status.
OADCO2Pos: T RO OAD position for CO2 control.
OADAutoPos: T RO Min of OADMinPos and free clg calc.
OADIndrFan: T RO Current OAD indoor fan calculation.
FreeClAvl: M RO
FreeClStrg: T RO Free cooling strategy being used.
FreeClEn: M RO Free cooling enabled calculation.
OADPosReset: T RO Min OAD reset calculation.
OADPosFreCl: T RO OAD free cooling PI loop output.
niOADMinPos: N RO Min OAD position override.
NetOADIn: N RO Client/Server OAD position.
NetEconEn: N RO Network economizer enable.
NetSpcCO2: N RO Network CO2 level in the space.
FaceBypassDamper
FBDmpr: N RO Face & bypass damper position.
FB_PIOut: T RO Face & bypass PI loop output.