OM 1280-2 • MICROTECH UNIT CONTROLLER 66 www.DaikinApplied.com
Menu Name
(Menu Index)
Minimum Password to Read
(None, User, Manager, Technician)
Minimum Password to Write
(None, User, Manager, Technician)
“RO” if Read Only
Help Text
DAT
DATSpt: N RO Current DAT setpoint.
DATClgSpt: N RO DAT Cooling setpoint.
DATHtgSpt: N RO DAT Heating setpoint.
AllHtStgsOn: T N Active if all heat stages are on.
AllHtStgsOf: T N
AirTmprgMod: M RO
DAHiLimMode: M RO
CmpAirTmprg: M RO Status of compressor heat air tempering.
DATRstClIn: M RO Value used in DAT Clg reset control.
DATRstHtIn: M RO Value used in DAT Htg reset control.
RstReHtIn: M RO DAT reset reheat input.
DATReHtSpt: M M DAT reheat setpt when NONE selected.
DATDehumSpt: M RO
DATReHtSpt: M RO DAT reset reheat setpoint.
NtDATReHtSp: N RO Network DAT reheat setpoint.
NtDATClgSpt: N RO Network DAT cooling setpoint.
NtDATHtgSpt: N RO Network DAT heating setpoint.
ElectricHeating
ElHtStgOut: T RO Number of elect ht stages currently on.
ElectHtAvl: N RO
ElHtCmdStgs: T RO Commanded electric heat stages.
ElDatLLPIOt: T RO Elect heat DAT LL PI loop output.
ElDatLLPIOutStg: T RO Convert ElDatLLPIOut to stages.
ElDehmPIOut: T RO Elect ht dehumid PI loop output.
ElDehumPIOutStg: T RO Convert ElectDehumPIOut to stages.
Humidity
N RO
N RO
OutEnth: M RO OA enthalpy using OAT and OA humidity.
InEnth: M RO IA enth using space temp and IA humid.
N RO Current humidity status of space.
KeyDehumEn: N M
DehumAvl: M RO
DehumEn: M RO Keypad or network dehumid enabled.
NetOutRH: N RO Network outside relative humidity.
NetSpcRH: N RO Network space relative humidity.
Timers
InStgTmr: N RO Seconds since state change occurred.
PmpOnTmr: N RO Seconds since pump was turned on.
RoomSensor
RSSysMode: N RO Room sensor mode status.
RSFanSpd: N RO Room sensor fan speed status.
RemSptAdjType: N T Remote sensor setpt adj type.
Password
PWLevel: N RO Current password level
EnterPW: N N Enter a new password.
KeyLUIOnStopPW: N M Current keypad On/Stop password level.
ClearPW: N U Clear the password level to NONE.
PWTimer: N - Password countdown timer.
Alarms|Active
Active Alarm #1 N RO
Uses LUIs GetText function with Index parameter to return one of up to 32
alarms.
AlmStat: N RO Active alarm status.
KeyRstAls: N U Keypad reset alarms.
TORstAlm: N RO Tenant override reset alarms.
TechSupport: N RO
Uses LUIs GetText function to return a whole screens-worth of data. Returns the
following: Alarms|Active
For Tech Support call 800-432-1342 or www.daikinapplied.com
AlmCfgStat: T RO
CntrlBoardStat: T RO Control board hardware alarm status.
MultAlmComp: T RO Active when a comp alarm is active.
Alarms|History
History Alarm #1 N RO
Uses LUIs GetText function with Index parameter to return one of up to 32
alarms.
TechSupport: N RO
Uses LUIs GetText function to return a whole screens-worth of data. Returns the
following: Alarms|Active
For Tech Support call 800-432-1342 or www.daikinapplied.com