OM 1280-2 • MICROTECH UNIT CONTROLLER 70 www.DaikinApplied.com
Menu Name
(Menu Index)
Minimum Password to Read
(None, User, Manager, Technician)
Minimum Password to Write
(None, User, Manager, Technician)
“RO” if Read Only
Help Text
Set|Defrost
DefChkTmSpt: N T How often to chk for defrst condition.
DefChkTm: N RO Time since last defrost cond check.
ASHPDefTime: N T ASHP defrost time setpt.
DefTmr: N RO Defrost timer countdown.
LwSctLnSpt: N T Low suction line temp alarm setpt.
T T
DefInFanSpt: T T
OACoilTempSpt: N T
T T
Set|Alarms
KeyRstFiltAl: N U
NetRstAls: N U Network reset alarms.
KeyRstAls: N U Keypad reset alarms.
FltrChgHrsSpt: N U Filter change alarm hours.
FltrChgHrsEn: N U Filter change alarm enable.
FltrChgHrs: N RO
DATLLAlTmSpt: N U All htg on this long before DATLL Alr.
ManAlTst: T T Manually test an alarm.
AlmBOcfg: T T Alarm binary out when Flt/Prob or Flt.
NetRstFiltAl: N U
Serv|OpHours
FanRunTm: N RO Fan run time.
CmpRunTm: N RO Compressor run time.
RstFanTm: T T Resets the total fan run time.
RstCmpTm: T T Resets the total compressor run time.
ServiceMode: T T Speeds-up certain timers.
ServiceTime: T T How long unit remains in Service Mode.
RestartCt: T T Number of controller restarts.
LastRstTyp: T T Last controller reset type.
Serv|SaveRestore
SaveCfsSel: T T
GetCfgsSel: T T
SaveUserRes: N RO
SaveParams: T T Manually save to non-volatile memory.
CfFileNumb: T T
T T
FactCfgStrg: T RO
SDStatus: N RO SD card is ready if status is Good.
RdWrStatus: N RO
Serv|AnaIn
Serv|AnaIn|Status
aiDAT: T RO Analog input discharge air temp.
aiRAT: T RO Analog input return air temp.
aiOAT: T RO Analog input outside air temp.
AnaIn10: T RO Analog input 10 counts.
aiLWT: T RO Analog input leaving water temp.
AnaIn12: T RO Analog input 12 counts.
CondOFlw: T RO
AnaIn14: T RO Analog input 14 counts.
OutAirFlw: T RO
HdPress: T RO Head pressure.
SptAdj: T RO Setpoint adjust temp.
RSSysMode T RO Remote sensor system mode value.
RSFanSpd: T RO Remote sensor fan speed mode value.
SpcTmpTO: T RO Space temp with tenant override.
HumIn: T RO Indoor humidity.
HumOut: T RO Outdoor humidity.
LnVlt: T RO Line voltage.
SpcTmp: T RO Space temp without tenant override.
CfgAnIn10: T T Select virtual function for ai10.
CfgAnIn12: T T Select virtual function for ai12.
CfgAnIn14: T T Select virtual function for ai14.
Serv|AnaIn|Virtual
CO2: T RO CO2 virtual input.
RstVlts: T RO Reset volts virtual input.
EWT: T RO Entering water virtual temp.
OutCoilTmp: T RO Outdoor coil virtual temp.
InCoilTmp: T RO Indoor coil virtual temp.
AVAILABLE
Serv|BinIn