www.DaikinApplied.com 69 OM 1280-2 • MICROTECH UNIT CONTROLLER
Menu Name
(Menu Index)
Minimum Password to Read
(None, User, Manager, Technician)
Minimum Password to Write
(None, User, Manager, Technician)
“RO” if Read Only
Help Text
EconPropGn: T T Economizer proportional gain.
EconIntgGn: T T Economizer integral gain.
CO2PropGn: T T CO2 proportional gain.
CO2IntgGn: T T CO2 integral gain.
N T
TemperEn: N M Air tempering mode enable.
OAMnPosExIlck: N T Min OAD when exhaust interlock active.
EOCLowOASpt: N T
RstMnVlts: T T aiCO2 at this val then reset RstMnVlts.
RstMxVlts: T T aiCO2 at this val then reset RstMxVlts.
RstMnUnits: T T PI out when aiCO2 is at RstMnVlts.
RstMxUnits: T T PI out when aiCO2 is at RstMxVlts.
SZnVAVMxDelta: T T Single zone VAV max delta.
SZnVAVMnFan: T T PI loop: Single zone VAV min fan.
SZnVAVMxFan: T T PI loop: Single zone VAV max fan.
SZnVAVPropGn: T T Single zone VAV proportional gain.
SZnVAVIntgGn: T T Single zone VAV integral gain.
OADLLPropGn: T T OAD lower limit proportional gain.
OADLLIntgGn: T T OAD lower limit integral gain.
OADLLInitPos: T T Initial lower limit OAD position.
OADLLPiDltOut: T T Lower limit OAD PI calculation.
SpcCO2En: N T Space CO2 enable.
OADCloseDly: N T
RstMnCO2: T T aiCO2 at this val then reset cpResetMinUnits.
RstMxCO2: T T aiCO2 at this val then reset cpResetMaxUnits.
Set|FaceBypassDampr
FBDPropGn: T T Face & bypass damper proportional gain.
FBDIntgGn: T T Face & bypass damper integral gain.
FBStrkTm: T T Time for FBP damper to swing open.
EWTFbAlrDly: T T
FBPMinPos: T T Face bypass min position.
Set|ServerClient
SClntType: T T
Set|HydroHeating
HtWtrPI: N RO Hot water PI loop output.
HtPropGn: T T Hydro htg valve proportional gain.
HtIntgGn: T T Hydro htg valve integral gain.
HtgMnPos: T T Output when temp delta is 0.
HtMxDeltTmp: T T Cntl and target delta for vlv at 100%.
HtMxPos: T T Output when delta is max delta temp.
CfgEwtRetryTime: T T Delay before retrying opening valve.
Set|HydroCooling
ColdWtrPI: N RO Cold water PI loop output.
ClPropGn: T T Hydro clg valve proportional gain.
ClIntgGn: T T Hydro clg valve integral gain.
ClMnPos: T T Output when temp delta is zero.
ClMxDeltaTmp: T T Cntl and target delta for vlv at 100%.
ClMxPos: T T Output when delta is max dlta temp.
Set|ExhaustFan
ExhStrtPos: N T Energize Exh fan OAD position setpt.