OM 1280-2 • MICROTECH UNIT CONTROLLER 68 www.DaikinApplied.com

Menu Name
(Menu Index)
Minimum Password to Read
(None, User, Manager, Technician)
Minimum Password to Write
(None, User, Manager, Technician)
“RO” if Read Only
Help Text
Set|Compressor
CmpMtrVlvTm: N T Motorize valve delay.
CmpMnOnTm: N T Compressor minimum on time.
󰀨 N T 󰀨
ClOATLckSpt: N T 
CmpHtOATLck: N T 
CmpHtEWTLck: N T 󰀨
󰀨 N T 󰀨
RevVlvTmr: T RO Rev vlv chgs this long after comp start.
Set|Timers
EWFlwTmSpt: N M Flow time before hydro ht/cl available.
MnStgTmSpt: N M Minimum state transition time.
ClStgTmSpt: N M Min time before clg stg chg can occur.
HtStgTmSpt: N M Min time before htg stg chg can occur.
NgtPrgTm: N M Night purge state time.
Set|Dehumid
SpcRHSpt: N M Space relative humidity setpoint.
󰀨 T M 󰀨
KeyDehumEn: N M 
DehumType: T T Active adds reheat.
DehumStgDn: T T 
PassDehumFBPD: T T F&B damper max for passive dehum.
NetDehumEn: N RO 
SpcRHEn: T T Space humidity sensor enable.
OutRHEn: T T Outdoor humidity sensor enable.
EnthSel: T T Select outdoor enthalpy calc strategy.
DehumFanSpt: T T 
DehumLTmpSpt: T T 
Set|DAT
DATClSpt: N M DAT cooling setpt when not reset.
DATHtSpt: N M DAT heating setpt when not reset.
DAEconLL: N T DAT Clg LL during non-comp cooling.
DAMechLL: N T Discharge air mech low limit setpt.
RehtLLStTime: T T Reheat to ReheatLL time.
DAHiLim: N T Discharge air high limit.
DATRstClSel: N T Source of DAT Clg reset control.
MnDATClSpt: T T Min input to DAT clg reset calc.
MxDATClSpt: T T Max input to DAT clg reset calc.
MnDATClCntSpt: T T Min DAT clg reset setpt.
MxDATClCntSpt: T T Max DAT clg reset setpt.
DATRstHtSel: N T Source of DAT Htg reset control.
MnDATHtSpt: T T Min input to DAT htg reset calc.
MxDATHtSpt: T T Max input to DAT htg reset calc.
MnDATHtCntSpt: T T Min DAT htg reset setpt.
MxDATHtCntSpt: T T Max DAT htg reset setpt.
DATClDb: T T DAT cooling deadband.
DATHtDb: T T DAT heating deadband.
RstReHtSel: T T DAT reset reheat select.
MnDATReHtSpt: T T Min input to DAT reheat reset calc.
MxDATReHtSpt: T T Max input to DAT reheat reset calc.
MnDATReHtCntSpt: T T Min DAT reheat reset setpt.
MxDATReHtCntSpt: T T Max DAT reheat reset setpt.
Set|ElectricHeat
ElHtPropGn: N T Electric heating proportional gain.
ElHtIntgGn: N T Electric heating integral gain.
ElHtStgTmSpt: T T Min time elect ht stg chg can occur.
MnElHtFanOnTm: T T Min fan on after leaving elect heat.
SupElHtSel: N M Allow elect heat to supplement primary.
Set|OutdoorDamper
OADMnPos: N M Min OAD for CO2 and fan at high speed.”
OADMnPosMdSpd: N M Min OAD when space fan at medium speed.”
OADMnPosLwSpd: N M Min OAD when space fan at low speed.”
SpcCO2Lim: N M Space CO2 setpoint.
EconOASpt: N M Economizer outdoor air setpoint.
󰀨 T T 󰀨
EconEnthSpt: N M Economizer enthalpy setpoint.
󰀨 T T 󰀨
OAMxPos: N T Maximum Outdoor Air damper position.
OALockEn: N M OA damper low temperature lockout.
OALockSpt: N T OA damper low temp lockout setpoint.
OATSpt: N M Economizer OAT setpoint.
EconEn: N M Keypad economizer enable.