Figure 98: Commission Unit Keypad/Display Menu Structure
OA Fan Set-Up
OA FAN STATUS
OA Fan1 Spd= XXX%
OA Fan1 Cmd= XXX%
OA Fan1Amps= XX.XA
Fault Code Details
OA Fan2 Spd= XXX%
OA Fan2 Cmd= XXX%
OA Fan2Amps= XX.XA
Fault Code Details
REFRIG CIRCUIT STATUS
PTS= XXX.Xpsi
PTD= XXX.Xpsi
Disch Sat Tmp= XXX.X°F
EffDshSatTSpt= XXX.X°F
OA Temp= XXX°F
INV Fin Temp= XXX°F
OA FAN SET UP
DischSatTDiff= 15°F
DischSatTDB= 2.0°F
OA Fan Period= 10s
OA Fan Gain= 0.5
OA Fan PAT= 20s
IFB COMM STATUS
Min OA Set-Up
Apply Changes= No FAN SPEED RESET
Min OA Reset= None Min Clg Spd= 40%
BSPOAOvrd= No Des Clg Spd= 100%
RstLmtSnsr= None BSP RESET
EXTERNAL RESET MinRFEFTm= 120s
OA @ MinV/mA= 0% BSP OvdST= 5s
OA @ MaxV/mA= 100% BSP OvdGain= 0.2
Min V/mA= 0.0V BSP OvdMaxChg= 4%
Max V/mA= 10.0V DAMPER LIMITING
CO2 RESET RstTLmt= 32.0ºF
IAQ Reset= Yes RstTSmplTm= 5s
PPM@DCVLmt= 800PPM RstTGain= 0.2
PPM@VntLmt= 1000PPM RstPAT= 60s
IAQ PPM= XXXXPPM RstTMaxChg= 4%
Min PPM= 0 PPM 0–30% OA Max= 30%
Max PPM= 2000 PPM Min Inc Rate= 0.03
V/A @Min PPM= 0.0/V Max Inc Rate= 1.0
V/A @Max PPM= 10.0/V
CFM RESET
OA Flow= XXXXXCFM
MinOAFlwSpt= 2000CFM
Field Stn Rst= Yes
Field Stn Cfg= VDC
Min CFM= 0 CFM
Max CFM= 10000 CFM
V/A @Min CFM= 0.0V
V/A @Max CFM= 10.0V
OA CFM DB= 3%
OA CFM Period= 30s
OA CFM Gain= 0.1
OA CFM Max Chg= 5%
Econo Set-Up
Clg Stage Time= 5min
Chgover Temp= 65.0°F
Clg DB= 2.0°F
Econo Period= 30s
Econo Gain= 10
Econo PAT= 60s
Econo Max Chg= 10%
Econo Diff= 2.0°F
Clg Reset= None
Min Clg Spt= 55.0°F
Min Clg Spt @= 0
Max Clg Spt= 65.0°F
Max Clg Spt@= 100
Heating Set-Up
Htg Stage Time= 5min
Htg DB= 2.0°F
Htg Period= 60s
Htg Gain= 0.8
Htg PAT= 120s
Htg Max Chg= 10%
Htg Lo OAT Lk= 0.0°F
Htg Hi OAT Lk= 55.0°F
EffHtgHiOATLk= 55.0°F
SuplHtgHiOATLk= 55.0°F
OAT Diff= 2.0°F
Htg Reset= None
Min Htg Spt= 55.0°F
Min Htg Spt @= 0
Max Htg Spt= 120.0°F
Max Htg Spt@= 100
Min DAT Ctrl= Yes
Min DAT Limit= 55.0°F
Occ Heating= Yes
Unocc Diff= 55.0°F
Htg Wmup Tm= 60s
Htg Hld Period= 240s
MWUSensor= RAT
Timer Settings
Service Time= 0min
Start Up= 180s
Recirculate= 180s
Zero OA Time= 0min
Tnt Override= 120min
Post Heat= 0s
Pwd Timeout= 10min
Low DAT= 6min
ClgStateDelay= 300s
Clg Stg Time= 5min
Htg Stg Time= 5min
MinExStrtTm= 120s
MinExStopTm= 120s
ER Whl Stg Tm= 5min
ER Whl Off Tm= 20min
Unit Set-Up
Space Sensor= Loc/Net
Eng Units= English
Unit Name= xxxxxxxxxxxx
Rapid Start= No
Rapid Start Tm= 10min
DO10 Clg= FanOp
SAF Set-Up
SAF Ctrl= DSP 1 ZONE VAV CONTROL CFM CONTROL
AplyInputChgs= No Min Clg Spd= 40% Min CFM= 0CFM
CO2 Input= None Max Clg Spd= 100% Max CFM= 10000CFM
CFM Input= None Min Htg Spd= 40% V/A @ Min CFM= 0V
BSP Input= No Max Htg Spd= 100% V/A @ Max CFM= 10 V
SPEED CONTROL Space Period= 30s SAF CFM DB= 3%
Rem SAF Cap= 25% Space Gain= 1.5 SAF CFM Period= 30s
DSP CONTROL Space PAT= 100s SAF CFM Gain= 0.1
DSP DB= 0.1in Space Max Chg= 10% SAF CFM MxChg= 5%
VFD Ramp Time= 60s CO2 CONTROL BSP CONTROL
Min Period= 5s Min PPM= 0PPM BSP DB= 0.01in
Max Spd Chg= 15% Max PPM= 2000PPM BSP Period= 5s
V/A @ Min PPM= 0V BSP Gain= 0.2
V/A @ Max PPM= 10V Max Spd Chg= 4%
Min SAF PPM= 800PPM SAF SETUP
Max SAF PPM= 1100PPM SAF Ctrl Dly= 30s
Min PPM Spd= 50% Min Speed= 25%
Max PPM Spd= 100% VAVBox Out= _________
Max Vent Speed= 100%
Max SAF RPM= 2600
ECM Status= _________
Commission Unit
Unit Set-Up
Timer Settings
SAF Set-Up
RF/EF Set-Up
Htg/Clg ChgOvr Set-Up
Cooling Set-Up
INV Cmp Set-Up
Econo Set-Up
Min OA Set-Up
Heating Set-Up
OA Fan Set-Up
Exp Valve Set-Up
Defrost Set-Up
Dehum Set-Up
Energy Rec Set-Up
D3 Set-Up
Alarm Conguration