3 | Components
Service manual
161
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
c
f
b
a dA
e
A Class 20~42 unit
a Power supply terminal X1M
b Power supply wiring bracket
c Screw (ground wire)
d Indoor unit main PCB
e Switch box screw
f Switch box
c
f
b
a dA
e
A Class 50~71 unit
a Power supply terminal X1M
b Power supply wiring bracket
c Screw (ground wire)
d Indoor unit main PCB
e Switch box screw
f Switch box
5 Disconnect the connectors of the indoor unit fan motor, the swing flap motor,
the swing raster motor and the streamer unit from the indoor unit main PCB.
6 Detach these wiring harnesses from the switch box.
7 Remove the screw and remove the switch box from the indoor unit.
8 To install the switch box, see "3.14Plate work"[4151].