After complete check of the indoor unit
main PCB, is the problem solved?
Action
No Replace the streamer unit, see "Repair
procedures"[4170].
3.16.2 Repair procedures
To remove the streamer unit
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see "3.14Plate work"[4151].
1 Disconnect the connector from the streamer unit.
b aA
A Wall mounted indoor unit
a Streamer unit connector
b Streamer unit
b aA
A Floor standing indoor unit
a Streamer unit connector
b Streamer unit
2 Click the streamer unit out of the indoor unit.
3 To install the streamer unit, see "Repair procedures"[4170].