55
TM-FLH--0515-C
Figure C
Floor Standing Type
PULL
PULL
PULL
PULL
2
Figure B
PULL
PULL
PULL
PULL
10mm or more
10mm or less
Utensils, Furnitures Or Built-In
Architectural Features Must Not
Protrude More Than 250.0mm
Ceiling Type
500mm or more
300mm or more
250mm or less
10mm or more
10mm or more
400mm or more
Please ensure that the following steps are taken:
• Check the gradient for drainage flow as
recommended in Figure B.
• Provide clearance for easy servicing and
optimal air flow as shown in Figure C.
• The indoor unit must be installed such that
there is no short circuit of the cool discharge
air with the warmreturn air.
• Do not install the indoor unit where there is
direct sunlight shining on the unit. The
location should be suitable for piping and
drainage installation. The unit must be a large
distance away from the door.