DANGER

Disconnect electric power before servicing equipment. More than one
disconnect may be required to de-energize the unit.
WARNING
Provide proper line voltage and phase balance.
Improper line voltage or excessive phase imbalance constitutes product
abuse. It can cause severe damage to the unit’s electrical components.
WARNING
.
Connect only low voltage NEC Class II circuits to terminal block TB2.
DANGER
  󰀨
      
death. Turn off the manual gas valve to the appliance before shutting off
the electrical supply.
Electrostatic Discharge (ESD)
Disconnect Power to the Rebel Rooftop Unit prior to
inspecting and/or repairing.



















All Units















 and also 

NOTE: 
dimensions.
Table 6: DPS 003–015, Recommended Field Power Wiring
Ampacity

Number of
Power Wires
Per Phase
Wire
Gauge
Insulation
Temperature

 1 14 75
25 1 12 75
35 1  75
 1 75
65 1 6 75
 1 4 75
 1 3 75
115 1 2 75
 1 1 75
 1  75
175 1  75
 1  75
 1  75
255 1  75
 1  75
 1  75
335 1  75
 1  75
 1  75
  
