Split Sky Air • Outdoor Units
12
Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B
4 Safety device settings
REQ71 125B
Model
Safety device
REQ71BV3 REQ100BV3 REQ125BW1
REQ71BW1 REQ100BW1
Fan motor thermal protector
Off 135 ±5°C
On 95 ±15°C
HPS
Off 4,15 Mpa
On 3.2 Mpa
LPS
Off -0.03 Mpa
On 0.05 Mpa
Max discharge temperature By thermistor and software control
Overcurrent relay By overcurrent sensor and software control
4TW26321-2B
+0
-0,10
+0,15
-0,15
+0,02
-0,02
+0,03
-0,03