1
11
Split Sky Air • Outdoor Units
34
Outdoor Units • R-410A • REQ-B8V3B_REQ-B8W1B
11 Installation
11 - 1 Installation method
4TW25149-8
REQ71 125B
Oil trap
Indoor unit
Oil trap
Gas piping
Liquid piping
Outdoor unit
Install trap at each difference in eight of 15m
NOTE:
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid
compression phenomenon, or cases of deterioration of oil return, it well be necessary to provide a trap at an appropriate
place in the riser gas piping.
A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.