EasyManuals Logo

Daikin RMX140JVMC8 User Manual

Daikin RMX140JVMC8
410 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #118 background imageLoading...
Page #118 background image
Si18-201 Refrigerant System and Function of Functional Parts of Outdoor Unit
Main Functions 105
 EVT : Motorized valve in non-operating room BP unit
In cooling operation, fully closed.
In heating operation, carries out the control equal to Super-multi unit control (entire system
control).
 EVH : Bypass motorized valve in BP unit
Opens at specified opening degree when oil collecting operation is conducted in heating
mode.
The EVH opens as well when oil collecting and defrosting operation is conducted in cooling
mode.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RMX140JVMC8 and is the answer not in the manual?

Daikin RMX140JVMC8 Specifications

General IconGeneral
BrandDaikin
ModelRMX140JVMC8
CategoryHeat Pump
LanguageEnglish

Related product manuals