SiBE31-801_C Troubleshooting by Indication on the Remote Controller
Troubleshooting 220
4. Troubleshooting by Indication on the Remote
Controller
4.1
A0
” Indoor Unit: Error of External Protection Device
Remote
Controller
Display
A0
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Detect open or short circuit between external input terminals in indoor unit.
Malfunction
Decision
Conditions
When an open circuit occurs between external input terminals with the remote controller set to
"external ON/OFF terminal".
Supposed
Causes
Actuation of external protection device
Improper field set
Defect of indoor unit PCB
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Actuation of external protection
device.
Change the second code No. to
"01" or "02" .
Replace the indoor unit PCB.
YES
YES
NO
NO
External protection
device is connected to
terminals T1 and T2 of
the indoor unit terminal
block.
ON/OFF input from
outside (mode No. 12,
first code No. 1) has
been set to external
protection device
input (second code
No. 03) by remote
controller.
Check the setting state of the
ON/OFF input from outside by
remote controller.

Table of Contents

Other manuals for Daikin RTSQ14PY1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RTSQ14PY1 and is the answer not in the manual?

Daikin RTSQ14PY1 Specifications

General IconGeneral
CategoryHeat Pump
ModelRTSQ14PY1
RefrigerantR32
Power Supply220-240V, 50Hz
Noise Level (Outdoor Unit)50 dB(A)

Related product manuals