Test Operation SiEN34-705
106 General Information
No. Setting item Description
30 Demand setting 1
Changes target value of power consumption when
demand control 1 is input.
32
Normal demand
setting
Normally enables demand control 1 without external
input. (Effective to prevent a problem that circuit breaker
of small capacity is shut down due to large load.)
35
Setting of difference
in elevation for the
outdoor unit
Make the setting when the outdoor unit is installed 40 m
or more below the indoor unit.
38
Emergency
operation
(Setting for the
master unit
operation
prohibition in multi-
outdoor-unit
system)
Used to temporarily prohibit the applicable outdoor unit
from operating should there be any faulty part in multi-
outdoor-unit system. Since the comfortable environment
is extremely impaired, prompt replacement of the part is
required.
39
Emergency
operation
(Setting for the
slave unit 1
operation
prohibition in multi-
outdoor-unit
system)
40
Emergency
operation
(Setting for the
slave unit 2
operation
prohibition in multi-
outdoor-unit
system)
42
Emergency
operation
(prohibition of INV
compressor
operation)
If the INV compressor has a failure, used to run the
system only with STD compressor(s). This is a temporary
running of the system until the compressor is replaced,
thus making comfort extremely worse. Therefore, it is
recommended to replace the compressor as soon as
possible.
(Be noted this setting is not available on model RXYQ5,
8PY1.)