VRV III Heat Pump: 50Hz/60Hz, Cooling Only: 50Hz
Connectable indoor units number and capacity
Normal Series
HP 5HP 8HP 10HP 12HP 14HP 16HP 18HP
System name RX(Y)Q5P RX(Y)Q8P RX(Y)Q10P RX(YQ12P RX(YQ14P RX(YQ16P RX(YQ18P
Outdoor unit 1 RX(Y)Q5P RX(Y)Q8P RX(Y)Q10P RX(Y)Q12P RX(Y)Q14P RX(Y)Q16P RX(Y)Q18P
Outdoor unit 2
Outdoor unit 3
Total number of connectable
indoor units
8 131619232629
Total capacity of connectable
indoor units (kW)
7.00~18.20 11.20~29.12 14.00~36.40 16.75~43.55 20.00~52.00 22.40~58.24 25.20~65.52
HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP
System name RX(Y)Q20P RX(Y)Q22P RX(Y)Q24P RX(Y)Q26P RX(Y)Q28P RX(Y)Q30P RX(Y)Q32P
Outdoor unit 1 RX(Y)Q8P RX(Y)Q10P RX(Y)Q8P RX(Y)Q8P RX(Y)Q10P RX(Y)Q12P RX(Y)Q16P
Outdoor unit 2 RX(Y)Q12P RX(Y)Q12P RX(Y)Q16P RX(Y)Q18P RX(Y)Q18P RX(Y)Q18P RX(Y)Q16P
Outdoor unit 3
Total number of connectable
indoor units
32 35 39 42 45 48 52
Total capacity of connectable
indoor units (kW)
27.95~72.67 30.75~79.95 33.60~87.36 36.40~94.64 39.15~101.79 41.95~109.07 44.70~116.22
HP 34HP 36HP 38HP 40HP 42HP 44HP 46HP
System name RX(Y)Q34P RX(Y)Q36P RX(Y)Q38P RX(Y)Q40P RX(Y)Q42P RX(Y)Q44P RX(Y)Q46P
Outdoor unit 1 RX(Y)Q16P RX(Y)Q18P RX(Y)Q8P RX(Y)Q8P RX(Y)Q8P RX(Y)Q8P RX(Y)Q10P
Outdoor unit 2 RX(Y)Q18P RX(Y)Q18P RX(Y)Q12P RX(Y)Q16P RX(Y)Q16P RX(Y)Q18P RX(Y)Q18P
Outdoor unit 3 RX(Y)Q18P RX(Y)Q16P RX(Y)Q18P RX(Y)Q18P RX(Y)Q18P
Total number of connectable
indoor units
55 58 61 64
Total capacity of connectable
indoor units (kW)
47.50~123.50 50.25~130.65 53.50~139.10 56.00~145.60 58.00~150.80 61.75~160.55 63.75~165.75
HP 48HP 50HP 52HP 54HP
System name RX(Y)Q48P RX(Y)Q50P RX(Y)Q52P RX(Y)Q54P
Outdoor unit 1 RX(Y)Q12P RX(Y)Q14P RX(Y)Q16P RX(Y)Q18P
Outdoor unit 2 RX(Y)Q18P RX(Y)Q18P RX(Y)Q18P RX(Y)Q18P
Outdoor unit 3 RX(Y)Q18P RX(Y)Q18P RX(Y)Q18P RX(Y)Q18P
Total number of connectable
indoor units
64
Total capacity of connectable
indoor units (kW)
67.50~175.50 69.50~180.70 71.50~185.90 73.50~191.10