EasyManua.ls Logo

Daikin RXQ8PY1 - Page 172

Daikin RXQ8PY1
355 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix SiEN34-705
166 General Information
Before turning on the power
Inspection item
Inspection method
Standard (guideline) Measurement values
Decision
Breaker capacity Visual inspection Specified capacity G NG
Refrigerant piping system
Gas detector No leaks G NG
Heat exchanger Visual inspection
No clogging or damage
G NG
Terminal connection section
Screwdriver, etc. No looseness G NG
Fan motor electrical insulation
500-V megatester
1 MΩ or more MΩ
Compressor electrical insulation
500-V megatester
1 MΩ or more
Installation Visual inspection Short circuit, etc. G NG
Refrigerant piping system
Gas detector No leaks G NG
Heat exchanger Visual inspection
No clogging or damage
G NG
Terminal connection section
Screwdriver, etc. No looseness G NG
Fan motor electrical insulation
500-V megatester
1 MΩ or more MΩ
Compressor electrical insulation
500-V megatester
1 MΩ or more
Installation Visual inspection Short circuit, etc. G NG
Refrigerant piping system
Gas detector No leaks G NG
Heat exchanger Visual inspection
No clogging or damage
G NG
Terminal connection section
Screwdriver, etc. No looseness G NG
Fan motor electrical insulation
500-V megatester
1 MΩ or more MΩ
Compressor electrical insulation
500-V megatester
1 MΩ or more
Installation Visual inspection Short circuit, etc. G NG
Indoor
unit
Refrigerant
system
Gas detector No leaks
Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NG
Room 5 G NG Room 6 G NG Room 7 G NG Room 8 G NG
Room 9 G NG Room 10 G NG Room 11 G NG Room 12 G NG
Room 13 G NG Room 14 G NG Room 15 G NG Room 16 G NG
Room 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG
Room 21 G NG Room 22 G NG Room 23 G NG Room 24 G NG
Room 25 G NG Room 26 G NG Room 27 G NG Room 28 G NG
Room 29 G NG Room 30 G NG Room 31 G NG Room 32 G NG
Room 33 G NG Room 34 G NG Room 35 G NG Room 36 G NG
Room 37 G NG Room 38 G NG Room 39 G NG Room 40 G NG
Air filter
Visual
inspection
No clogging or
damage
Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NG
Room 5 G NG Room 6 G NG Room 7 G NG Room 8 G NG
Room 9 G NG Room 10 G NG Room 11 G NG Room 12 G NG
Room 13 G NG Room 14 G NG Room 15 G NG Room 16 G NG
Room 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG
Room 21 G NG Room 22 G NG Room 23 G NG Room 24 G NG
Room 25 G NG Room 26 G NG Room 27 G NG Room 28 G NG
Room 29 G NG Room 30 G NG Room 31 G NG Room 32 G NG
Room 33 G NG Room 34 G NG Room 35 G NG Room 36 G NG
Room 37 G NG Room 38 G NG Room 39 G NG Room 40 G NG
Heat exchanger
Visual
inspection
No clogging or
damage
Room 1 G NG Room 2 G NG Room 3 G NG Room 4 G NG
Room 5 G NG Room 6 G NG Room 7 G NG Room 8 G NG
Room 9 G NG Room 10 G NG Room 11 G NG Room 12 G NG
Room 13 G NG Room 14 G NG Room 15 G NG Room 16 G NG
Room 17 G NG Room 18 G NG Room 19 G NG Room 20 G NG
Room 21 G NG Room 22 G NG Room 23 G NG Room 24 G NG
Room 25 G NG Room 26 G NG Room 27 G NG Room 28 G NG
Room 29 G NG Room 30 G NG Room 31 G NG Room 32 G NG
Room 33 G NG Room 34 G NG Room 35 G NG Room 36 G NG
Room 37 G NG Room 38 G NG Room 39 G NG Room 40 G NG
System name
Outdoor unit 1
INV MΩ
STD1 MΩ
STD2 MΩ
Outdoor unit 2
Outdoor unit 3

Table of Contents

Related product manuals