SiEN34-705 Test Operation
General Information 89
4.4.1.2 Infrared Remote Control - Indoor Unit
BRC7C type
BRC7E type
BRC4C type
1. When in the normal mode, push the “ ” button for 4 seconds or more, and operation
then enters the “field set mode.”
2. Select the desired “mode No.” with the “ ” button.
3. Pushing the “ ” button, select the first code No.
4. Pushing the “ ” button, select the second code No.
5. Push the timer “ ” button and check the settings.
6. Push the “ ” button to return to the normal mode.
(Example)
When setting the filter sign time to “Filter Dirtiness-High” in all group unit setting, set the Mode
No. to “10”, Mode setting No. to “0” and setting position No. to “02”.
Mode No.
Field set mode
Second code no.
First code no.