SiBE041134 Forced Cooling Operation
Trial Operation and Field Settings 165
2. Forced Cooling Operation
Indoor Unit
Outdoor Unit
Item Forced Cooling
Conditions The forced cooling operation is allowed when both of the following conditions
are met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start The forced cooling operation starts when any of the following conditions is fulfilled.
1) Press the forced cooling operation [ON/OFF] button (SW1) on the indoor
unit for 5 seconds.
2) Press the forced cooling operation [ON/OFF] button (SW1) on the outdoor
unit with standby electricity saving function turned off.
Command
frequency
58 Hz
End The forced cooling operation ends when any of the following conditions is fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation [ON/OFF] button (SW1) on the indoor
unit again.
3) Press the [ON/OFF] button on the remote controller.
4) Press the forced cooling operation [ON/OFF] button (SW1) on the outdoor
unit.
Others Protection functions have priority over all other functions during forced cooling
operation.
[ON/OFF] button (SW1)