EasyManuals Logo

Daikin RXS20K3V1B User Manual

Daikin RXS20K3V1B
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
Troubleshooting SiBE041134
76 Service Diagnosis
Troubleshooting
Correct the power supply.
Replace the outdoor
unit PCB.
Check for such factors for a
long term.
Try to restart a few times.
(R16043)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NO
YES
NO
YES
YES
Reconnect the harness.
Check the power supply voltage.
Check the connection of the
compressor harness.
Disturbance factors
Noise Power supply distortion
Repeat a few
times.
(Precaution before turning on the power again)
Make sure the power has been off for at
least 30 seconds.
Replace the indoor
unit PCB.
Turn on the
power again. System
restarted?
Error
again within 3 minutes
after turning on the
power?
Loose or
disconnected?
Voltage as rated?
YES
NO

Table of Contents

Other manuals for Daikin RXS20K3V1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RXS20K3V1B and is the answer not in the manual?

Daikin RXS20K3V1B Specifications

General IconGeneral
BrandDaikin
ModelRXS20K3V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals