Service Check Function SiBE121021_C
292 Service Diagnosis
6. Press the Mode button.
The figure of the one’s place blinks.
7. Press the Temp or button and change the figure until you hear the sound of “beep”.
8. Diagnose by the sound.
“pi” : The figure of the ten’s place does not accord with the error code.
“pi pi” : The figure of the ten’s place accords with the error code but the one’s not.
“beep” : The both figures of the ten’s and one’s place accord with the error code.
9. Determine the error code.
The figures indicated when you hear the “beep” sound are error code.
(Error codes and description
Refer to page 306, 307.)
10.Press the Mode button for 5 seconds to exit from the service check mode.
(When the remote controller is left untouched for 60 seconds, it returns to the normal mode
also.)