21 | Configuration
Installer and user reference guide
135
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
For the content or reason behind the malfunction code see "25.3Solving problems
based on error codes" [4 159], where most relevant malfunction codes are
explained. Detailed information about malfunction codes can be consulted in the
service manual of this unit.
[1‑40] [1‑41]
Code Shows ...
[1‑40] The current cooling comfort setting
[1‑41] The current heating comfort setting
See "21.2 Energy saving and optimum operation" [4 140] for more details about
this setting.
21.1.7 Mode 2: field settings
[2‑8]
T
e
target temperature during cooling operation.
[2‑8] T
e
target [°C]
0 (default) Auto
2 6
3 7
4 8
5 9
6 10
7 11
For more information and advice about the impact of these settings, see
"21.2Energy saving and optimum operation"[4140].
[2‑9]
T
c
target temperature during heating operation.
[2‑9] T
c
target [°C]
0 (default) Auto
1 41
2 42
3 43
4 44
5 45
6 46
For more information and advice about the impact of these settings, see
"21.2Energy saving and optimum operation"[4140].
[2‑12]
Enable the low noise function and/or power consumption limitation via external
control adaptor (DTA104A61/62).