21 | Configuration
Installer and user reference guide
138
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
[2‑27] Stop time automatic low noise operation
(approximately)
3 (default) 8h00
[2‑30]
Power consumption limitation level (step 1) via the external control adaptor
(DTA104A61/62).
If the system needs to be running under power consumption limitation conditions
when an external signal is sent to the unit, this setting defines the level power
consumption limitation that will be applied for step1. The level is according to the
table.
[2‑30] Power consumption limitation (approximately)
1 60%
2 65%
3 (default) 70%
4 75%
5 80%
6 85%
7 90%
8 95%
[2‑31]
Power consumption limitation level (step 2) via the external control adaptor
(DTA104A61/62).
If the system needs to be running under power consumption limitation conditions
when an external signal is sent to the unit, this setting defines the level power
consumption limitation that will be applied for step2. The level is according to the
table.
[2‑31] Power consumption limitation (approximately)
1 (default) 40%
2 50%
3 55%
[2‑32]
Forced, all time, power consumption limitation operation (no external control
adaptor is required to perform power consumption limitation).
If the system always needs to be running under power consumption limitation
conditions, this setting activates and defines the level power consumption
limitation that will be applied continuously. The level is according to the table.
[2‑32] Restriction reference
0 (default) Function not active.
1 Follows [2‑30] setting.
2 Follows [2‑31] setting.
[2‑35]
Height difference setting.