Page #102 background image
SiE39-404 Special Control
Function 91
3.6 Stopping Operation
3.6.1 When System is in Stop Mode
* Actuators are based on RXYQ16M.
Actuator Operation
Compressor OFF
Outdoor unit fan OFF
Four way valve Holds ON
Main motorized valve (EV1) 0 pls
Subcooling motorized valve (EV2) 0 pls
Hot gas bypass valve (SVP) OFF
Oil equalization valve (SVO) OFF
Receiver gas discharging valve (SVG) OFF
Non-operating unit liquid pipe stop valve (SVSL) ON
Ending conditions Indoor unit thermostat is turned ON.