10 Technical data
Installation and operation manual
29
RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543426-1 – 2018.07
a
b
a
c
d
a
b
a
e
d
e
c
a
b
a
e
d
f
c
a
b
a
e
b
d
c
a
b
a
e
d
f
c
Layout A+B+C+D A+B
Possibility 1 Possibility 2
1 a≥10mm
b≥300mm
c≥10mm
d≥500mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
a≥200mm
b≥300mm
2 a≥10mm
b≥300mm
c≥10mm
d≥500mm
e≥20mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
e≥100mm
a≥200mm
b≥300mm
e≥400mm
3 a≥10mm
b≥300mm
c≥10mm
d≥500mm
e≥20mm
f≥600 mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
e≥100mm
f≥500mm
—
4 a≥10mm
b≥300mm
c≥10mm
d≥500mm
e≥20mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
e≥100mm
5 a≥10mm
b≥500mm
c≥10mm
d≥500mm
e≥20mm
f≥900mm
a≥50mm
b≥500mm
c≥50mm
d≥500mm
e≥100mm
f≥600mm
—
ABCD Sides along the installation site with obstacles
F Front side
Suction side
▪ In case of an installation site where sides A+B+C+D have
obstacles, the wall heights of sides A+C have no impact on
service space dimensions. Refer to the figure above for impact of
wall heights of sides B+D on service space dimensions.
▪ In case of an installation site where only the sides A+B have
obstacles, the wall heights have no influence on any indicated
service space dimensions.
▪ The installation space required on these drawings are for full load
heating operation without considering possible ice accumulation. If
the location of the installation is in a cold climate, then all
dimensions above should be >500 mm to avoid accumulation of
ice in between the outdoor units.
INFORMATION
The service space dimensions in above figure are based
on cooling operation at 35°C ambient temperature
(standard conditions).
INFORMATION
Further specifications can be found in the technical
engineering data.
10.2 Piping diagram: Outdoor unit
Piping diagram: RXMLQ8 + RXYLQ10~14
R3T
R8T
R21T
R6T
R5T
R1T
R4T
d
c
b
c
d
h
l
i
f
n
o
m
g
j
e
k
a
p
M2F
M
M1F
M
R7T
R10T
M1C
Y5S
Y4S
S1NPL
S1NPH
S1PH
SV
SV
SV
SV
a Compressor (M1C)
b Heat exchanger
c Fan
d Fan motor (M1F, M2F)
e Accumulator